🔧 HVAC CFM Chart Tool
Metal Duct Calculator - Size by Friction Rate or Velocity
Calculation Parameters
Calculation Results
Enter your parameters and click "Calculate" to see results
Quick Reference Guide
Standard Round Duct Sizes
3", 4", 5", 6", 7", 8", 9", 10", 12", 14", 16", 18", 20", 22", 24", 26", 28", 30", 32", 34", 36"
Velocity Guidelines
Supply Ducts: 600-1200 FPM
Return Ducts: 400-800 FPM
Main Trunk: 900-1400 FPM
Friction Rate Guidelines
Typical Range: 0.05-0.15" wc/100ft
Low Pressure: 0.05-0.08" wc/100ft
High Pressure: 0.10-0.15" wc/100ft
HVAC Duct Sizing Guide: How to Use Ductulators & Duct Calculators with Duct2Go
Improper HVAC duct sizing, too large or too small, creates the same costly problems as installing the wrong HVAC unit. Uneven temperatures, noisy systems, and rising energy bills are all symptoms of ducts that aren’t measured and designed correctly.
That’s why HVAC contractors and facility managers turn to duct sizing calculators (ductulators) to get accurate airflow measurements. At Duct2Go, we help you not only fabricate custom sheet metal ductwork to exact specifications, but also give you the tools and resources to size ducts properly before you order.
Why Correct Duct Sizing Matters
Choosing the wrong duct size can:
- Prematurely wear out HVAC components
- Cause poor airflow and uncomfortable rooms
- Lead to customer callbacks and warranty issues
- Increase long-term energy costs
For HVAC businesses, that means unhappy clients and reduced profit margins. With Duct2Go’s precision-built ducts, you can deliver better installs, fewer issues, and long-term system efficiency.
How to Calculate Duct Size
1. Measure Square Footage
Start with the square footage of each individual room, not just the total building. For example, a 10×10 room equals 100 square feet. For irregular shapes, divide the space into sections and add them up.
2. Determine Air Velocity (CFM)
Airflow is measured in cubic feet per minute (CFM). Using a Manual J load calculation, you’ll find the BTUs required for each room. Then, calculate duct CFM with:
Room CFM = (Room load ÷ Whole house load) × Equipment CFM
As a rule of thumb, 1 CFM covers about 1 to 1.25 sq. ft. of floor space, though sunny rooms or those with large windows may need closer to 2 CFMs.
3. Select the Right HVAC Unit
Divide the building’s BTU load by 12,000 to find required tonnage. For example, 24,000 BTUs ÷ 12,000 = 2 tons. Then, multiply tonnage by 400 CFM (average output) to determine system airflow.
4. Calculate Friction Loss & Static Pressure
Use the formula:
Friction Rate = (Available Static Pressure × 100) ÷ Total Effective Length (TEL)
This tells you how much pressure drop your system can handle, guiding your duct size and layout choices.
5. Consider Duct Material
Sheet metal ducts provide the least airflow resistance compared to flex or fiberglass duct board. With Duct2Go’s galvanized sheet metal fabrication, you get the durability and airflow consistency needed for residential and commercial installs.
Why Contractors Choose Duct2Go
✔ Custom Fabrication – Round, rectangular, and spiral ducts built to SMACNA standards
✔ Fast Turnaround – Reduce project delays with quick lead times
✔ Nationwide Delivery – Reliable shipping for contractors and builders across the U.S.
✔ Made in the USA – High-quality sheet metal, cut and fabricated locally
When paired with accurate duct sizing, Duct2Go ductwork ensures system efficiency, customer satisfaction, and long-term energy savings.
Grow Your HVAC Business with Duct2Go
The right duct sizing is only part of the equation. You need a fabricator that delivers precise, code-compliant ducts every time. That’s where Duct2Go comes in!